6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 570 -
*Note: The user can set the type of the output signal. When
Var
is set for scheme switch
[
DPSY01-PLSM
], the output period of the signal is defined by the setting
[
DPSY01-CPW
]. When
Fix
is set, the signal ceases when the 43-switch is changed.
††
Note: To identify the input and output signal-points of the DPSY02 logic, see Table
4.2-15 for PLC#1, Table 4.2-16 for PLC#2, Table 4.2-20, and Table 4.2-21 for
output signals.
‡‡
Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [
DPSY01-RST
] has been reached.
Output signal to BO
The DPSY01 function, in Figure 4.2-20, can issue an “Operate” signal at the output point
“DPSY01_OEX_BO”, when the DPSY01 function determines that the received signal “Remote-
Closing-Control” is true.
(ii)
Receiving “operate command Open” from the remote-end
Figure 4.2-21 depicts the reception of the operate command ‘Open’ from the remote-end.
Signal reception in
IEC61850
Operate command Open from the remote-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Wait for a command
Signal output
Operate command Closing l from the local-end
Operate command Open from the local-end
Operate command Closing from the remote-end
Operate command Closing by the PLC function
Operate command Open by the PLC function
Wait for a next command
Select stage
Select command Open from the remote-end
Select command Closing from the remote-end
Select command Open from the local-end
Select command Closing from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-21 Outline of operate command ‘Open’
Mapping required for Input point from communication
Figure 4.2-22 illustrates the operate logic when an “Operate command (Remote-Open-Control)”
signal is applied to the DPSY01 logic. The input-point “DEV01_CONTROL_REQ” is used for
the reception of the “Operate command Open (Remote-Open-Control)”.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......