background image

 

  1 

V1.05

 

VG-6777 Digital Isolate Interface 

Installation and Operation Manual V1.05

 

Features 

Easy Installation

Loop power supply

Both side

 isolate control

Designed to comply with EN 54-17

Description 

VG-6777 Digital Isolate Interface monitors the 

short circuit fault at the loop detection zone ,It 

has both side isolate function ,if detects the 

short circuit on loop it will isolate that side to   

ensure loop communication signal will not be affected or interrupt by short-circuit fault. When the short circuit fault is 

removed, the isolate interface will automatically restore loop. 

Technical data 

Operating Voltage: 

18-28V(Modulated-pulse)

Standby Current: 

1mA 

Isolate holding current 

10mA 

Action condition 

Isolate input/output side short circuit or loop voltage 

7.5V

 

Wiring 

Two-wire

non-polarized

 

Temperature range: 

-10

℃~

50

Humidity: 

95%RH, 

40

±

2

℃)

No condensation 

Isolate Indication: 

Active A or Active B 

LED illuminates steadily. 

IP Rating: 

32 

Installation Base 

VG-6618 

Note:

The VG-6777 Isolate interface is working with V-GREAT Digital Protocol 

Installation 

Dimensions

Showing on Fig.1

Fig.1 