6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1185 -
For example, to let a device execute “Select”, “Operate” and “Cancel” commands
from the sever through “CSWI4” and transmit the information to an IED, the user
should map an input point (Data ID) to several variables of “CSWI4” (See Figure
11.3-22). Mapping period for Control shall be 100.
*Note: For more information of the input points, see chapter
General control function or
Control and monitoring application, if available.
Input DataID
DE V01_ CONTROL_ RE Q
SBOW
Oper
Cancel
Mapping
Figure 11.3-22 Control function mapping
To complete the setting for control function, after mapping data, the user needs
to set BI, BO† in the GR-TIEMS ->Setting.
†Note: For more information for the BI, BO, see Chapter
Technical description: Binary IO
module.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......