6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 707 -
(iii)
Purpose of Quality information in the output signal
In the output signal, the quality information will affect the control of the device. Table 4.7-3
shows four types of output signal. When the quality information (Quality) of an output signal
issued by a node is indicated as being “NG”, it signifies that device control is forbidden. On the
other hand, quality information (Quality) “OK” means that that device control is allowed.
Table 4.7-3 Device status, quality information in the output signal
Output signal
(stVal–Quality)
Meaning
0–OK
Control forbidden
0–NG
Control forbidden
1–OK
Control allowed
1–NG
Control forbidden
Note: With regard to the value of ‘Quality’, we define “OK” as ‘0’ and “NG” as ‘1’ in the
logic operation.
AND interlock operator
When quality information (Quality) is applied to the interlock operator “AND”, the “AND”
operator outputs the quality information intact. That is, the output quality information is not
affected by device status (stVal). Table 4.7-4 shows two-input-signals (A, B) and the output
signal for “AND”.
Table 4.7-4 Output signals (stVal–Quality) for AND
Input B (stVal–Quality)
0–OK 0–NG 1–OK 1–NG
Input A
(stVal–Quality)
0–OK 0–OK
–
–
–
0–NG 0–OK 0–NG
–
–
1–OK 0–OK 0–NG 1–OK
–
1–NG 0–OK 0–NG 1–NG 1–NG
Figure 4.7-5 shows the logic symbol for the interlock operator “AND” with input signals
and an output signal. Figure 4.7-5 can be represented by equations (4.7-11) and (4.7-12).
stVal = stVa(A) • stVa(B)
(4.7-11)
Quality=(Quality(A)+Quality(B))•(stVa(A)+ Quality(A))
•(stVa(B)+Quality(B))
(4.7-12)
For example, when the interlock operator “AND” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–OK) using the equations (4.7-11) and (4.7-12). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the AND operator; the AND
operator produces zero (0) which is defined as “OK” in ‘Quality’. A note regarding the values
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......