6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 708 -
used for ‘Quality’ can be found immediately below Table 4.7-3.
stVal
Quality
stVal
Quality
AND (
•
)
Output
Input(A)
Input(B)
stVal
Quality
Figure 4.7-5 Logic of interlock operator (AND) and Input/Output signals
OR interlock operator
When quality information (Quality) is applied to the interlock operator “OR”, the quality
information is affected by device status (stVal). Table 4.7-5 shows two-input-signals (A, B) and
the output signal for “OR”
Table 4.7-5 Output signals (stVal–Quality) of OR
Input B (stVal–Quality)
0–OK 0–NG 1–OK 1–NG
Input A
(stVal–Quality)
0–OK 0–OK
–
–
–
0–NG 0–NG 0–NG
–
–
1–OK 1–OK 1–OK 1–OK
–
1–NG 1–NG 1–NG 1–OK 1–NG
As shown in Table 4.7-5, if ‘0’ represents the status value “stVal” for all input signals, and
if the quality information of “NG” is given for an input signal, then the output signal “Quality”
is represented as “NG”. On the other hand, if all input signals “stVal” are represented by “1”,
and if the quality information for the input signals “stVal(1)” is given, then the representation
“OK” can be weighted for the output signal “Quality” . Note that quality information (OK) for
input signals with “stVal(1)” get priority if there are two or more input signals, which are
represented as “stVal(1)”.
Figure 4.7-6 shows the logic symbol for the interlock operator “OR” with input signals and an
output signal, which can be represented by equations (4.7-13) and (4.7-14).
stVal
Quality
stVal
Quality
OR (+)
Output
Input(A)
Input(B)
stVal
Quality
Figure 4.7-6 Interlock operator (OR) and Input/Output signals
stVal=stVa(A)+stVa(B)
(4.7-13)
Quality=!((stVal(A)•!Quality(A))•(stVa(B)•!Quality(B))+
!(stVal(A)+Quality(A)+stVal(B)+Quality(B)))
(4.7-14)
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......