6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 802 -
How to add another select condition signal
If adding another condition is required, the user can add a signal to the select condition logic
using the PLC condition point “User Additional Condition”.
1.
Add a user-preferred signal using TPOS01IN_TMP_24, which is listed as PLC#1 in
Table 4.9-8.
2.
Set the scheme switch [
TPOS01-LGSLFFCT
] to
Fixed logic
.
Select condition
TPOS01 function (Function ID: 513001)
User configurable condition (PLC#2 connection point)
Fixedlogic
[
TPOS01-LGSLFFCT
]
To selection logic
Control hierarchy (e.g. 43RL) (PLC#3 connection point) *10
IED serious error detected
[
TPOS01-CTREN
]
On
Users must setup this condition correctly
Function
“Automatic sequence control” is in progress
Additional condition (PLC#1 connection point)
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
Tripping
*
4
(“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN. TRIP
TPOS01IN_TMP_24
513001 800401EE61
TPOS01IN_TMP_25
513001 810401EE62
TPOS01IN_TMP_21
513001 820401ED50
SERI_ERR
&
&
&
&
1
≥
1
≥
Unmatched condition detected *5
Event suppression detected *6
= TPOS01_QLT_SPP
BI board connection error detected*7
= TPOS01_QLT_BI_ERR
(513001 8204011F59)
(513001 8604011F5A)
OFF
[
SCDEN
]*8
Same Directional
Controlling Event
&
P1-control command received
TPOS01_ST_P1
&
TPOS01_ST_P2
P2-control command received
&
TPOS01_ST_P3
P3-control command received
&
&
[
TPOS01-DEVTYPE
]
*9
EDS
(513001 8304011D02)
(513001 8104011D03)
(513001 8504011D04)
“EDS” never permit to control
from “P1 to P3” and “P3 to P1”.
Figure 4.9-20 Select condition logic for ‘P1–P3 control’ in TPOS01*
11
*1
Note:
“Command Blocking” disables any operation except its own; the “Command
blocking” is initiated by the status of “CBK” in a software switch controller
(SOFTSW). The IEC 61850 standard defines “Command Blocking” as “CmdBlk”.
For more information of “CBK”, see Chapter
Control and monitoring application:
Software switch control. See the signal “CBK_STATE” of Table 4.9-6.
*2
Note:
“Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......