6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 628 -
†Note: To identify the input and output signals of the other SOFTSW logics, see Table
4.3-12, Table 4.3-13, and Table 4.3-14.
‡Note: “operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
(v)
Receiving “operate command On” using PLC logic
Figure 4.3-19 shows the logic when an “Operate command (PLC-ON-Control)” signal is applied
to the SOFTSW1 logic. The input signal is generated using the user-programmed PLC logic;
the user can connect the signal for the PLC connection point “S4301_CHG_TO_ON”.
SOTFSW1 function (Function ID: 522001)
OFF to ON
Operate Command
Operate condition
‡
ASEQ function
§
” is in progress
ASEQ_MULTI_SEL
&
&
Input
Output
Operate logic in SOFTSW1
“S4301_OEC_CHG_PLC”
(522001
_
8C0A041F5D)
522001
_
810A041D03
&
S4301_ST_ON
Operate completed
“S4301_PLC_CTRL_FAIL”
(522001
_
870A041F62)
Operate failed
d
S4301_CHG_TO_ON
522001 850A04EDE1
ON-control command
(PLC connection point #1)
“S4301_EX_SS”
(522001
_
870A041F62)
1.0s
0
t
Figure 4.3-19 ‘ON’ Operation logic using PLC logic
†
†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-3, Table 4.3-13, Table 4.3-15, Table 4.3-16, and Table 4.3-17.
‡Note: “operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
(vi)
Receiving “operate command Off” using PLC logic
Figure 4.3-20 shows the logic when an “Operation command (PLC-Off-Control)” signal is
applied to the SOFTSW1 logic. The input signal is generated using the user-programmed PLC
logic; the user can connect the signal for the PLC connection point “S4301_CHG_TO_OFF”.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......