6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 622 -
5
Note: Criteria “unmatched conditions” are decided when “Test-bit status” in command is
not identical to “IED test status”.
6
Note: The user will need to program the PLC logic “Control hierarchy condition”. The
Control hierarchy condition provided by the user-programmed PLC logic may be
43R/L; the user can connect it at PLC connection point “S4301_CTRL_RIGHT” of
(viii)
Signal name and number
Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.3-3 PLC connection point #1 (Inputs point for ‘On’ control)
Signal Number
Signal Name
Description
M/O
522001 850A01EDE1
CBK_CHG_TO_ON
PLC ON control for CBK
O
522001 850A02EDE1
ICB_CHG_TO_ON
PLC ON control for ICB
O
522001 850A03EDE1
SCB_CHG_TO_ON
PLC ON control for SCB
O
522001 850A04EDE1
S4301_CHG_TO_ON
PLC ON control for SOFTSW1 (S43-01)
O
522001 850A05EDE1
S4302_CHG_TO_ON
PLC ON control for SOFTSW2 (S43-02)
O
522001 850A06EDE1
S4303_CHG_TO_ON
PLC ON control for SOFTSW3 (S43-03)
O
….
…..
….
522001 850A40EDE1
S4361_CHG_TO_ON
PLC ON control for SOFTSW61 (S43-61)
O
Table 4.3-4 PLC connection point #2 (Input points for ‘Off’ control)
Signal Number
Signal Name
Description
M/O
522001 860A01EDE0
CBK_CHG_TO_OFF
PLC OFF control for CBK
O
522001 860A02EDE0
ICB_CHG_TO_OFF
PLC OFF control for ICB
O
522001 860A03EDE0
SCB_CHG_TO_OFF
PLC OFF control for SCB
O
522001 860A04EDE0
S4301_CHG_TO_OFF
PLC OFF control for SOFTSW1 (S43-01)
O
522001 860A05EDE0
S4302_CHG_TO_OFF
PLC OFF control for SOFTSW2 (S43-02)
O
522001 860A06EDE0
S4303_CHG_TO_OFF
PLC OFF control for SOFTSW3 (S43-03)
O
….
…..
….
522001 860A40EDE0
S4361_CHG_TO_OFF
PLC OFF control for SOFTSW61 (S43-61)
O
Table 4.3-5 PLC connection point #3 (Input points on select condition logic)
Signal Number
Signal Name
Description
M/O
522001 820A01ED50
CBK_CTRL_RIGHT
Control hierarchy condition in CBK
M
522001 820A02ED50
ICB_CTRL_RIGHT
Control hierarchy condition in ICB
M
522001 820A03ED50
SCB_CTRL_RIGHT
Control hierarchy condition in SCB
M
522001 820A04ED50
S4301_CTRL_RIGHT
Control hierarchy condition in SOFTSW1 (S43-01)
M
522001 820A05ED50
S4302_CTRL_RIGHT
Control hierarchy condition in SOFTSW2 (S43-02)
M
522001 820A06ED50
S4303_CTRL_RIGHT
Control hierarchy condition in SOFTSW3 (S43-03)
M
….
…..
….
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......