ELM & ELM2 EMERGENCY LIGHTING RECALL  

INSPECTION & CIRCUIT BOARD REPLACEMENT INSTRUCTIONS

CAUTION:   Read and follow Important Safeguards carefully before proceeding.

ELM2 —

 with adjustable lamps

ELM —

 with stationary, fixed-optic lamps

Patent # US D473,672

US D483,511

US D484,272

Patents pending

This recall does not include the following light unit models: 

•  ELM2 SD 

 

•  ELM2 LED 

•  ELM2 WRS 

Check the label inside your unit to verify the model number.

Call Acuity Brands Lighting with any questions: 888.615.4501

The two circuit board revisions that are covered by this recall look like this:

Rev. C

Rev. B

1.  READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
2.  Turn off electricity at fuse or circuit breaker before proceeding.
3.  All work should be performed by qualified personnel.
4.  For installation and maintenance instructions please go to www.lithonia.com.

IMPORTANT SAFEGUARDS

Содержание ELM

Страница 1: ...ing light unit models ELM2 SD ELM2 LED ELM2 WRS Check the label inside your unit to verify the model number Call Acuity Brands Lighting with any questions 888 615 4501 The two circuit board revisions...

Страница 2: ...e circuit boards that are beige on one or both sides like the one depicted below are NOT part of the recall Press both circular snaps at the bottom of the housing Rotate the housing upward and pull i...

Страница 3: ...re installed Note Some circuit boards have a single rectangular chip and some have two smaller rectangular chips Inspect the circuit board components B Repeat steps 1 2 for every emergency lighting u...

Страница 4: ...mounting plate is loose contact Acuity Brands Lighting at 800 334 8694 for a replacement mounting plate Inspect the internal contacts for black oxidation discoloration If any damage is present contac...

Страница 5: ...inuous AC power being provided Allow the battery to charge for 48 hours for full charge After full battery recharge press the test switch Both lampheads should illuminate If one or more lamps do not i...

Страница 6: ...SAFEGUARDS ON FRONT COVER SHEET 6TH STEP REMOVING AND REPLACING RECALLED CIRCUIT BOARD ONCE REPLACEMENT BOARD HAS BEEN RECEIVED Remove the affected emergency lighting units from the wall Refer to you...

Страница 7: ...which will be disconnected in the next step BOTH ELM ELM2 units Disconnect the blue battery connector at the circuit board located at the BLUE BATT terminal Use needle nosed pliers to unplug the batt...

Страница 8: ...s will be discarded with only the red wire attached Destroy and discard recalled circuit board F 7TH STEP INSTALLING THE NEW CIRCUIT BOARD Use needle nosed pliers to connect the blue wire terminal by...

Страница 9: ...edge connectors will point toward the open back of the fixture The snaps should click when the circuit board is fully seated The board as properly installed is shown in the photo in the 8th step Inser...

Страница 10: ...e B Apply continuous power to the unit The test switch indicator light should illuminate red Caution Battery must be connected to the light unit prior to applying AC power Damage to the battery will o...

Страница 11: ...ELM ELM2 EMERGENCY LIGHTING UNIT RECALL INSPECTION CIRCUIT BOARD REPLACEMENT INSTRUCTIONS 11 Wiring Diagram for reference Part EMCSA00852 rev A...