6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 586 -
The DPSY01 function can issue a “Result” signal at the output point “DPSY01_SLD_CSCN”.
(iii)
Operate condition for the counter
Figure 4.2-36 illustrates the operate condition logic. The DPSY01 function can determine an
operate-condition using a signal received from “Control hierarchy”. The Control hierarchy
condition is provided by user-programmed PLC logic (i.e., 43R/L); the user must connect the
control-hierarchy with the DPSY01 function using connection point “DPSY01IN_TMP_47” (see
Table 4.2-26).
Operate condition
To counter logic
From Control hierarchy
DPSY01IN_TMP_47
511001 800201ED5A
&
1
≥
DPSY01 function (Function ID: 511001)
Detection of serious errors
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
DCB RCV OR
Traveling OR
SERI_ERR
Unmatched condition detected *4
= DPSY01_SC_ST_ERR
From CMNCTRL
Figure 4.2-36 Operate condition logic for changing the counter in DPSY01
1
Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of “CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter
Control and
monitoring application: Software switch controller. See the signal
““S4301_STATE” of Table 4.2-7.
2
Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3
Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detecting signal is denoted
as “Travelling OR” in Table 4.2-7.
4
Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......