6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 416 -
2.27.3
Decision of DS open/close status
The PROT_COMMON function can determine the behavior and position status of a DS. Signal
configuration and settings for the DS position status are similar to that of the CB. Note that
settings and logics cited below are just available for the DS.
(i)
Signal selection
Set either
NO
,
NC
, or
Both
for scheme switch [
DS-Contact
].
(ii)
Contact supervision
When
Both
is set for scheme switch [
DS-Contact
], the auxiliary switch contact state of the DS
is supervised. Set
On
for scheme switch [
DS-SV
] when contact supervision is required. The
supervision period has to be set between 0 to 100 seconds for the setting [
TDSSV
].
(iii)
Logic
Figure 2.27-2 shows the logic used to determine DS status and generates the output signal of
the DS state: DS_CLOSE or DS_OPEN. The supervision scheme logic to supervise the status
of the DS auxiliary switch contacts. This scheme logic is applied when
BOTH
is set for the
scheme switch [
DS-Contact
]. For the operation, the user should inject signals of DS states for
the following PLC connection points: ‘DS-NO CONT’, ‘DS NC CONT’ and others.
1
≥1
8C0000EBBD DS-NC_CONT
≥1
&
NC
DS-Contact
DS_CLOSE
8C0000EBB6 DS-NO_CONT
&
≥1
NO
Both
1
8E00001B85
DS_OPEN
8F00001B86
0
–100s
t 0
8C00001BB6
8C00001BBD
=1
1
&
TDSSV
DS-FAIL
8C00001B9B
DS-SV
Both
&
To STUB-OC
Figure 2.27-2 Scheme logic to determine DS status
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......