The recording function consists of three recording features: (1) Fault recorder, (2) Event
recorder, and (3) Disturbance recorder. The fault recorder collects the information about the
power system quantities when a fault occurs. The event recorder groups state information
when the changes are detected. The disturbance recorder is designed to memory the various
quantities—numerical analog data and logic data (binary data)—from the monitoring function
and the BIO modules; it is possible to analyze the disturbance using the engineering tool (GR-
TIMES), which can draw several chronological waves.
Fault recorder
During the fault, the fault recorder can memorize reasons by equipment failures/operation
states, system information etc. It commences by injecting a signal coming from the TRC alarm-
signal generation logic, but is also started by a trigger provided by PLC function. The fault
recorder captures the following items for each fault:
Date and time at the fault
Tripped phase information
Operating mode information
FL calculation result (if the FL function operates)
Evolving faults (if the ARC function operates)
Fault and pre-fault quantities
8.1.1
Types of recording information
The fault recorder can cyclically memory past eight faults; the oldest memory will be erased
cyclically if another fault occurs. The memorized information has 1ms accuracy. If a fault
occurs, the fault recorder is directed to operate to memory operating modes etc. about the fault.
(i)
Date and time at fault
The date and time at the fault is recorded. The date and time information is provided by the
clock function (see Chapter
Technical description: Clock function
).
(ii)
Tripped phase information
Information about tripped phases (i.e., faulted phases) are recorded using the recording
identifiers (‘OPT-PHASE-A,B,C, and -N’ signals), which the TRC function provides.
(iii)
Mode information
At the occurrence of a fault, the protection functions gives the fault recorder the reasons of
tripping; the reasons are brought using operation identifiers† and logical signals‡. The fault
recorder can have up to 192 of all identifiers and signals in the IED. The operation identifiers
are chosen using the settings [
OP Mode ID1
] to [
OP Mode ID128
]. The settings [
OP Mode
ID201
] to [
OP Mode ID264
] are used for general purposes to record the logical signals.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......