6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 593 -
operation of the detection function from Time ‘A’ (e.g., Time ‘A’ to Time ‘C’).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [
DPSY-TELR
]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time ‘D’ to ‘E’).
To initiate event suppression the user should set
On
for scheme switch [
DPSY01-SPPEN
].
(ii)
BO connection for
“select command Open/Closing”
Figure 4.2-43 exemplifies the connection for the select command Open/Closing. Suppose that
connection with the BOs is achieved by the PLC function using connection points
“DPSY01_OSL_BO_FLG” and “DPSY01_FSL_BO_FLG”†; as a result, the “Select command
Closing” and the “Select command Open” signals are issued at BO1 and BO2 respectively.
BO1_SOURCE
200B01 310200E11D
Select logic in DPSY01
PLC connection point on BO1
Select logic for Select Command
Closing in DPSY01
Select logic for Select Command
Open in DPSY01
≥1
&
[
BO1_CPL
]
Off
On
&
DRIVER BO1
Signal captured by
setting [
Input signal 1
]
[
Input signal 2
]
[
Input signal 3
]
[
Input signal 4
]
[
Input signal 5
]
[
Input signal 6
]
[
Input signal 7
]
[
Input signal 8
]
Select
Command
Closing
≥1
“BO1”
(200B01
_
8002001112)
“BO1-RB”
(200B01
_
8002001113)
BO1 circuit at IO#1(Function ID: 200B01)
Terminal and
wire
To contact health
check
Connected by
“Programming”
To contact health
check
BO2_SOURCE
200B01 310201E11D
PLC connection point on BO2
≥1
&
[
BO2_CPL
]
Off
On
&
DRIVER BO2
Signal captured by
setting [
Input signal 1
]
[
Input signal 2
]
[
Input signal 3
]
[
Input signal 4
]
[
Input signal 5
]
[
Input signal 6
]
[
Input signal 7
]
[
Input signal 8
]
≥1
“BO2”
(200B01
_
8102011112)
“BO2-RB”
(200B01
_
8102011113)
BO2 circuit at IO#1 (Function ID: 200B01)
Terminal and
wire
To contact health
check
Connected by
“Programming”
To contact health
check
“DPSY01_OSL_BO_FLG”
(5110018602011DC6)
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
Select
Command
Open
Figure 4.2-43 Example for select commands connection with BO1 & BO2 at IO#1
†Note: Table 4.2-10 shows the remaining signals with the excepting
“DPSY01_OSL_BO_FLG” and “DPSY01_FSL_BO_FLG”.
(iii)
BO connection for
“operate command Open/Closing”
Figure 4.2-44 exemplifies the connection for “Operate command Closing” or “Operate command
Open”. Suppose that connection with the BOs is achieved by the PLC function using connection
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......