6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 627 -
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
(iii)
Receiving “operate command On” from the local end
Figure 4.3-17 shows the logic when an “Operate command (Local-ON-Control)” signal is
applied to the SOFTSW1 logic. The input signal is provided when “Execution of On” key is
pressed on the IED front panel.
SOFTSW1 function (Function ID:
522001)
OFF to ON
Operate Command
Operate condition
‡
ASEQ function
§
” is in progress
ASEQ_MULTI_SEL
&
&
Input
Output
Operate logic in SOFTSW1
“S4301_OEC_CHG”
(522001
_
890A041F5A)
522001
_
810A041D03
&
S4301_ST_ON
Operate completed
“S4301_EX_SS”
(522001
_
870A041F62)
0
t
1.0s
Operate failed
d
Command
“Local-On-Control”
Figure 4.3-17 ‘ON’ Operation logic at local in SOFTSW1
†
†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-11, Table 4.3-13, and Table 4.3-15.
‡Note: “operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
(iv)
Receiving “operate command Off” from the local end
Figure 4.3-18 shows the logic when an “Operation command (Local-OFF-Control)” signal is
applied to the SOFTSW1 logic. The input signal is provided when “Execution for Off” key is
pressed on the IED front panel.
SOFTSW1 function (Function ID:
522001)
ON to OFF
Operate Command
Operate condition
‡
ASEQ function
§
” is in progress
ASEQ_MULTI_SEL
&
&
Input
Output
Operate logic in SOFTSW1
“S4301_FEC_CHG”
(522001
_
8A0A041F5B)
522001
_
830A041D02
&
S4301_ST_OFF
Operate completed
“S4301_EX_SS”
(522001
_
870A041F62)
0
t
1.0s
Operate failed
d
Command
“Local-Off-Control”
Figure 4.3-18 ‘OFF’ Operation logic at local in SOFTSW1
†
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......