6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 558 -
(vi)
Receiving “Select command Open” by PLC function
Figure 4.2-11 outlines the reception of the select command ‘Open’ by the PLC function.
PLC logic programmed
by the user
Select command Open by the PLC function
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Open from the remote-end
Select command Closing from the remote-end
Select command Open from the local-end
Select command Closing from the local-end
Select command Closing by the PLC function
Figure 4.2-11 Outline of select command ‘Open’
Input signal from the PLC function
Figure 4.2-12 shows the select logic when a “Select command Open (PLC-Open-Control)” signal
is generated by the PLC function There are two input-points for the reception of this signal,
unlike in the signal “Select command Closing (PLC-Closing-Control)” where four are available.
That is, if interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2:e.g., DEV01_OP_COMMAND). PLC#1 and the PLC#2 are shown in
Table 4.2-4.
DPSY01 function (Function ID: 511001)
“DPSY01_FSL_BO_CSF”
(511001
_
8A02011DC4)
DEV01_OP_INTERLOCK
Operation command
without ILK condition
ILK
† condition (“Open”) passed
PLC in DIR operate
For DIR operation
511001 800201EE31
Signals from user PLC logic
Output
Select logic in DPSY01
0.1s
0
t
&
&
&
Select condition
1
≥
Open-control command requiring ILK checking
(PLC#1 connection point)
DEV01_OP_COMMAND
511001 800201EE30
Open-control command requiring no ILK checking
(PLC#2 connection point)
Operation command
with ILK condition
DPSY01-Open
Select
“Failed”
To BO connection
Select
“success”
To
“Wait for a command”
For DIR operation
Figure 4.2-12 Select Open by PLC function in DPSY01
††
††
Note: To identify the input and output points of the DPSY02 logic, see Table 4.2-4 for
the inputs (PLC#1 and PLC#2) and Table 4.2-11 for the outputs.
Output signal to BO
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......