6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 561 -
7
Note: A supervision of the Binary IO module can detect connection errors for BI circuits
.
8
Note: The Common control (CMNCTRL) function can test and check the ‘Opening’ and
‘Closing’ operations performed by the logic. When the user sets
Off
for scheme
switch [
SCDEN
], the operation of the logic is blocked if the logic is running in the
same operation-direction compared with the previous operation-direction (i.e.,
when closing (opening) is performed sequentially). On the other hand, if
On
is set
for the scheme switch, the logic is not blocked.
9
Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point “DPSY01IN_TMP_28”. For more information, see
Chapter
Control and monitoring application: Control hierarchy. See PLC#3 of
10
Note:
To identify the input points of the DPSY02, see Table 4.2-8.
(viii)
Signal name and number
Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.2-3 PLC connection points (Input points for Command ‘Closing’)
Signal Number
Signal Name
Description
M/O
5A0101 800527EF40
DEV01_CL_SYNC_INTER DPSY01 PLC Close-control checking with interlock & Sync (PLC#1)
O
5A0101 800551EF40
DEV02_CL_SYNC_INTER DPSY02 PLC Close-control checking with interlock & Sync (PLC#1)
O
5A0101 800526EF40
DEV01_CL_SYNC
DPSY01 PLC Close-control with Sync (PLC#2)
O
5A0101 800550EF40
DEV02_CL_SYNC
DPSY02 PLC Close-control with Sync (PLC#2)
O
5A0101 800525EF40
DEV01_CL_INTERLOCK
DPSY01 PLC Close-control checking with interlock(PLC#3)
O
5A0101 800549EF40
DEV02_CL_INTERLOCK
DPSY02 PLC Close-control checking with interlock(PLC#3)
O
5A0101 800524EF40
DEV01_CL_COMMAND
DPSY01 PLC Close-control none checking (PLC#4)
O
5A0101 800548EF40
DEV02_CL_COMMAND
DPSY02 PLC Close-control none checking (PLC#4)
O
Table 4.2-4 PLC connection points (Input points for Command ‘Open’)
Signal Number
Signal Name
Description
M/O
5A0101 800523EF40
DEV01_OP_INTERLOCK
DPSY01 PLC Open-control checking with interlock(PLC#1)
O
5A0101 800547EF40
DEV02_OP_INTERLOCK
DPSY02 PLC Open-control checking with interlock(PLC#1)
O
5A0101 800522EF40
DEV01_OP_COMMAND
DPSY01 PLC Open-control without checking(PLC#2)
O
5A0101 800546EF40
DEV02_OP_COMMAND
DPSY02 PLC Open-control without checking(PLC#2)
O
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......