6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 595 -
Setting for “Select command Closing”
For example, the point “DPSY01_OSL_BO_FLG” is connected to the BO1 circuit for the issuing
of the command; the user can connect point “BO1-RB” with the contact health check function
using the setting [
DPSY01-OSLBORD
]. Do not key the point “DPSY01_OSL_BO_FLG”.
“DPSY01_OSL_BO_FLG”
(511001 8602011DC6)
Selection logic in
DPSY01
&
Signal connected by
setting [
DPSY01-OSLBORD
]
“BO1-RB”
(200B01
_
8002001113)
BO1 circuit at
IO#1
Contact health check
logic in DPSY01
Result of contact
health check
Connection made by the user
Figure 4.2-45 Example connection of “Select command Closing” for the health check feature
Setting the “Select command Open”
Similar to “select command Closing”, the point “DPSY01_FSL_BO_FLG” is connected with the
BO2 circuit; the user is required to key point “BO2-RB” for the setting [
DPSY01-FSLBORD
].
Do not key the point “DPSY01_FSL_BO_FLG”.
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
Selection logic in
DPSY01
&
Signal connected by
setting [
DPSY01-FSLBORD
]
“BO2-RB”
(200B01
_
8102001113)
BO1 circuit at
IO#1
Contact health check
logic in DPSY01
Result of contact
health check
Connection made by the user
Figure 4.2-46 Example connection of “Select command Open” for the health check feature
Setting for “Operate command Closing”
Similarly, the point “BO3-RB” must be applied for the setting [
DPSY01-OEXBORD
].
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......