6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 581 -
Operate condition
User configurable operate condition (PLC#2 connection point)
Same Directional
Controlling Event
OFF
[SCDEN]*8
Fixedlogic
[
DPSY01-
LGEXFFCT
]
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point)*9
[
DPSY01-CTREN
]
On
Additional condition (PLC#1 connection point)
DPSY01IN_TMP_40
511001 800201EE65
DPSY01IN_TMP_41
511001 810201EE66
DPSY01IN_TMP_28
511001 820201ED50
Command
“Closing-control” received
Command
“Open control” received
received
&
&
&
&
&
&
1
≥
1
≥
DPSY01_3PH_STATE
DPSY01 function (Function ID: 511001)
Function
“Automatic sequence control” is in progress
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
Tripping
*
4
(“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN. TRIP
Unmatched condition detected *5
Event suppression detected *6
= DPSY01_F_QLT_SPP
BI board connection error detected*7
= DPSY01_F_BI_ERR
(511001 8102011F5F)
(511001 8202011F60)
IED serious error detected
SERI_ERR
Users must setup this condition correctly
(511001 3102011001)
Figure 4.2-31 Operate condition logic for ‘Closing/Open’ in DPSY01
1
Note: “Command Blocking” disables any operation except for itself; “Command
Blocking” is implemented as “CBK” in a software switch controller (SOTFSW).
The IEC 61850 standard defines “Command Blocking” as “CmdBlk”. For more
information on “CBK”, see Chapter
Control and monitoring application: Software
switch controller. See the signal ““S4301_STATE” in Table 4.2-7.
2
Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3
Note: Detection of event “device-travelling”, signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the event is detected. The detection signal is denoted as
“Travelling OR” in Table 4.2-7.
4
Note: If an IED is in the process of issuing a trip command, all control operation is
blocked until the trip operation has been completed. If the IED has a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
5
Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to the “IED test status”.
6
Note: The “Event suppression” function can detect chattering in BI circuits. (See section
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......