6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 924 -
Table 5.4-4 Setting items for binary input circuits in the variable type (i.e., BI2A module)
Setting devices
Range
Uni
ts
Contents
Default
Common
BI1-3_PICKUP
18 to 222
V Guaranteed-minimum-pick-ups at BI1, BI2, and BI3
77
BI4-6_PICKUP
18 to 222
V Guaranteed-minimum-pick-ups at BI4, BI5, and BI6
77
BI7-9_PICKUP
18 to 222
V Guaranteed-minimum-pick-ups at BI7 to BI9
77
BI10-12_PICKUP
18 to 222
V Guaranteed-minimum-pick-ups at BI10 to BI12
77
CMP_NUM
4 to 9
– Number of times in the filter
4
BI1_CPL
Off/On
– Switch for programmable operation in BI1
Off
BI1
On Delay Timer 0.000 to 300.000 s Value in the on-delay timer
0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse – Inversion operation of BI1 signal
Normal
BI2_CPL
Off/On
– Switch for programmable operation in BI 2
Off
BI2
On Delay Timer 0.000 to 300.000 s Value in the on-delay timer
0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse – Inversion operation of BI2 signal
Normal
BI3_CPL
Off/On
– Switch for programmable operation in BI 3
Off
BI3
On Delay Timer 0.000 to 300.000 s Value in the on-delay timer
0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse – Inversion operation of BI3 signal
Normal
…..
…..
…..
…..
…..
BI
n
_CPL
Off/On
– Switch for programmable operation in BI
n
Off
BI
n
4
On Delay Timer 0.000 to 300.000 s Value in the on-delay timer
0.000
Off Delay Timer 0.000 to 300.000 s Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse – Inversion operation of BIn signal
Normal
4
Note: BI1_CPL~BI12_CPL settings are provided for the BI2A module.
As an example, Figure 5.4-1 shows the binary input circuit of the BI1A in order to help
understand the settings. The BI1A consists of 18 binary input circuits and each circuit has
three settings:
Setting threshold level
Comparison feature for contact chatter
CPL switches (“Delayed pick-up and delayed drop-off signal” and “Logic level
inversion”), used as basis of input signal characteristics.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......