6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 830 -
Operate condition
TPOS01 function (Function ID: 513001)
User configurable condition (PLC connection point#2)
Fixedlogic
[
TPOS01-LGSLFFCT
]
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point#3) *10
IED serious error detected
[
TPOS01-CTREN
]
On
Users must setup this condition correctly
Function
“Automatic sequence control” is in progress
Additional condition (PLC connection point #1)
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
Tripping
*
4
(“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN. TRIP
TPOS01IN_TMP_33
513001 800401EE65
TPOS01IN_TMP_34
513001 810401EE66
TPOS01IN_TMP_21
TPOS01IN_TMP_41
513001 820401ED50
SERI_ERR
&
&
&
&
1
≥
1
≥
Unmatched condition detected *5
Event suppression detected *6
= TPOS01_QLT_SPP
BI board connection error detected*7
= TPOS01_QLT_BI_ERR
(513001 8204011F59)
(513001 8604011F5A)
OFF
[
SCDEN
]*8
Same Directional
Controlling Event
&
P1-control command received
TPOS01_ST_P1
&
TPOS01_ST_P2
P2-control command received
&
TPOS01_ST_P3
P3-control command received
&
&
[
TPOS01-DEVTYPE
]
*9
EDS
(513001 8304011D02)
(513001 8104011D03)
(513001 8504011D04)
“EDS” never permit to control
fr
om “P1 to P3” and “P3 to P1”.
Figure 4.9-44 Operate condition logic for P1–3 control in TPOS01*
11
*1
Note:
“Command Blocking” disables any operation except for itself; “Command
blocking” is implemented as “CBK” in a software switch controller (SOFTSW);.
The IEC 61850 defines “Command Blocking” as “CmdBlk”. For more information
of “CBK”, see Chapter
Control and monitoring application: Software switch
control function. See the signal “CBK_STATE” in Table 4.9-6.
*2
Note:
“Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
*3
Note:
Detection of event “device-travelling signifies that other operators are
changing the status of one or more devices. Thus, device operation by the IED
should be inhibited whilst ever the event is detected. The detection signal is
denoted as “Traveling OR” in Table 4.9-6.
*4
Note:
If an IED is in the process of issuing a trip command, all control operation is
blocked until the trip operation has been completed. If the IED has a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......