6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 878 -
*
4
The operation state turns to OFF, when the control logic cancels the
selection of Device#1 following the reception of a stop command from
the ASEQ01 function.
Operating state
Selection signal for Device #2
Selection signal for Device #3
Selection signal for Device #1
*
1
The ASEQ01 function generates a selection signal for
the emergency stop for the control logic.
*
2
The ASEQ01 function generates an emergency
command for the control logic.
*
3
The control logic turns the selection
signal to OFF when the control signal is
not sent for the device.
ON
OFF
Figure 4.11-4 Time chart of automatic sequence when emergency stop command is applied
during the operation of Device#1
4.11.4
Control hierarchy conditions
The user should program the “Control hierarchy” for the ASEQ01 function. The user should
connect the condition with the select condition logic using the connection point
“ASEQ01IN_TMP_28”. For more information, see Chapter
Control and monitoring application:
Control hierarchy
. Table 4.11-8 shows the respective points in the ASEQ functions.
Table 4.11-8 Control hierarchy points on ASEQ functions
Signal Number
Signal Name
Description
M/O
523001 820D01ED50
ASEQ01IN_TMP_28
ASEQ01 control hierarchy condition
M
523001 820D02ED50
ASEQ02IN_TMP_28
ASEQ02 control hierarchy condition
M
523001 820D03ED50
ASEQ03IN_TMP_28
ASEQ03 control hierarchy condition
M
…
…
…
523001 820D0FED50
ASEQ15IN_TMP_28
ASEQ15 control hierarchy condition
M
Table 4.11-9 Control hierarchy point for Emergency stop
Signal Number
Signal Name
Description
M/O
523001 820D10ED50
EMERSTOPIN_TMP_28
Emergency control for stopping the operation
M
4.11.5
Input for emergency stop
The ASEQ functions are able to receive an “EMERSTOP_EXEC_STOP” command (see Table
4.11-3); the user should program to acquire the sign so that the ASEQ logics can abandon for
controlling devices. The operation will stop instantly even if the control logic is waiting for
some condition (i.e., synchronization or others).
Table 4.11-10 PLC monitoring points (Outputs for ASEQ emergency status)
Signal Number
Signal Name
Description
523001 000D0D1001
EMERSTOP_ACC_EXEC
Reception of an emergency signal
523001 800D0D1D58
EMERSTOP_EC_LCD
Emergency signal generated on the LCD scream
523001 800D0D1D55
EMERSTOP_EC_OWS
Emergency signal generated from OWS(HMI)
523001 800D0D1D56
EMERSTOP_EC_RCC
Emergency signal generated from RCC
523001 800D0D1D57
EMERSTOP_EC_RMT
Emergency signal generated at Remote
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......