Output terminals
8.2 Analog outputs
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
297
8.2.1
Lists of signals for the analog outputs
Signals for the analog outputs: vector object
Table 8-1
List of signals for the analog outputs - vector object
Signal
Parameter
Unit
Scaling (100 %=...)
See table below
Speed setpoint before the setpoint filter
r0060
rpm
p2000
Motor speed unsmoothed
r0061
rpm
p2000
Actual speed smoothed
r0063
rpm
p2000
Output frequency
r0066
Hz
Reference frequency
Output current
r0068
Aeff
p2002
DC link voltage
r0070
V
p2001
Torque setpoint
r0079
Nm
p2003
Output power
r0082
kW
r2004
For diagnostic purposes
Control deviation
r0064
rpm
p2000
Modulation depth
r0074
%
Reference modulation depth
Torque-generating current setpoint
r0077
A
p2002
Torque-generating actual current
r0078
A
p2002
Flux setpoint
r0083
%
Reference flux
Actual flux
r0084
%
Reference flux
For further diagnostic purposes
Speed controller output
r1480
Nm
p2003
I component of speed controller
r1482
Nm
p2003
Scalings for vector object
Table 8-2
Scalings for vector object
Variable
Scaling parameter
Default for quick commissioning
Reference speed
100 % = p2000
p2000 = Maximum speed (p1082)
Reference voltage
100 % = p2001
p2001 = 1000 V
Reference current
100 % = p2002
p2002 = Current limit (p0640)
Reference torque
100 % = p2003
p2003 = 2 x rated motor torque
Reference power
100 % = r2004
r2004 = (p2003 x p2000 x π) / 30
Reference frequency
100 % = p2000/60
Reference modulation depth
100 % = Maximum output voltage
without overload
Reference flux
100 % = Rated motor flux
Reference temperature
100% = 100°C