Mechanical installation
3.3 Installation
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
37
Fitting a hood to increase the degree of protection to IP23/IP43/IP54 (option M23/M43/M54)
1.
Remove the crane transport assembly (if fitted).
2.
Make sure that a perforated top cover is not fitted on the top of the cabinet (depending on
production requirements, this can be fitted at a later stage).
3.
Options M43 and M54 only:
Use the sealing tape provided to attach the contact surfaces of the hood to the top of the
cabinet.
4.
Fit the hood to the roof of the cabinet at the positions specified (fixing points for the crane
transport assembly).
,QVHUWWKHRULJLQDOKRRG
VFUHZV0IURPDERYH
,QVHUWWKHHQFORVHG
VFUHZVDQGSODLQZDVKHUV0
IURPEHORZ
$GGLWLRQDOVFUHZVKHUHIRU
ZLGHKRRGV
Figure 3-2
Attaching a hood