Electrical installation
4.9 Other connections
Drive converter cabinet units
68
Operating Instructions, 07/07, A5E00288214A
Table 4-18 Accommodating the voltage limiting network in the cabinet or in an additional cabinet
Voltage range
Installation of the dV/dt filter
with Voltage Peak Limiter
within the converter cabinet
unit
Installation of the VPL in an
additional cabinet, 400 mm
width
Installation of the VPL in an
additional cabinet, 600 mm
width
380 V - 480 V 3 AC
6SL3710-7LE32-1AA0
6SL3710-7LE32-6AA0
6SL3710-7LE33-1AA0
6SL3710-7LE33-8AA0
6SL3710-7LE35-0AA0
6SL3710-7LE36-1AA0
6SL3710-7LE37-5AA0
6SL3710-7LE38-4AA0
6SL3710-7LE41-0AA0
6SL3710-7LE41-2AA0
6SL3710-7LE41-4AA0
660 V to 690 V 3 AC
6SL3710-7LH28-5AA0
6SL3710-7LH31-0AA0
6SL3710-7LH31-2AA0
6SL3710-7LH31-5AA0
6SL3710-7LH31-8AA0
6SL3710-7LH32-2AA0
6SL3710-7LH32-6AA0
6SL3710-7LH33-3AA0
6SL3710-7LH34-1AA0
6SL3710-7LH34-7AA0
6SL3710-7LH35-8AA0
6SL3710-7LH37-4AA0
6SL3710-7LH38-1AA0
6SL3710-7LH38-8AA0
6SL3710-7LH41-0AA0
6SL3710-7LH41-3AA0
500 V to 690 V 3 AC
6SL3710-7LG28-5AA0
6SL3710-7LG31-0AA0
6SL3710-7LG31-2AA0
6SL3710-7LG31-5AA0
6SL3710-7LG31-8AA0
6SL3710-7LG32-2AA0
6SL3710-7LG32-6AA0
6SL3710-7LG33-3AA0
6SL3710-7LG34-1AA0
6SL3710-7LG34-7AA0
6SL3710-7LG35-8AA0
6SL3710-7LG37-4AA0
6SL3710-7LG38-1AA0
6SL3710-7LG38-8AA0
6SL3710-7LG41-0AA0
6SL3710-7LG41-3AA0
Constraints
The following constraints should be noted when a dV/dt filter with a Voltage Peak Limiter is
used:
●
The output frequency is limited to no more than 150 Hz.
●
Maximum permissible motor cable lengths:
–
Shielded cable: max. 300 m
–
Unshielded cable: max. 450 m
Commissioning
During commissioning, the dV/dt filter with Voltage Peak Limiter must be logged on using
STARTER or the AOP30 operator panel (p0230 = 2).
Note
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.