Functions, monitoring, and protective functions
9.4 Extended functions
Drive converter cabinet units
352
Operating Instructions, 07/07, A5E00288214A
Commissioning
The "extended monitoring functions" function module can be activated by running the
commissioning wizard. Parameter r0108.17 indicates whether it has been activated.
Function diagram
FD 8010
Speed messages
FD 8013
Load monitoring
Parameters
•
p2150
Hysteresis speed 3
•
p2151
CI: Speed setpoint
•
p2161
Speed threshold 3
•
p2181
Load monitoring, response
•
p2182
Load monitoring, speed threshold 1
•
p2183
Load monitoring, speed threshold 2
•
p2184
Load monitoring, speed threshold 3
•
p2185
Load monitoring, speed threshold 1 upper
•
...
•
p2190
Load monitoring, speed threshold 3 lower
•
p2192
Load monitoring, delay time
•
r2198.4
BO: ZSW monitoring 2, |n_setp| ≤ p2161
•
r2198.5
BO: ZSW monitoring 2, n_setp < 0