Electrical installation
4.9 Other connections
Drive converter cabinet units
88
Operating Instructions, 07/07, A5E00288214A
Connection
Table 4-36 Terminal block -A1-A140 – connection for evaluation unit PT100 resistors
Terminal
Designation
Technical specifications
T11-T13
90–240 V AC/DC; PT100; sensor 1; group 1
T21-T23
90–240 V AC/DC; PT100; sensor 2; group 1
T31-T33
90–240 V AC/DC; PT100; sensor 3; group 1
T41-T43
90–240 V AC/DC; PT100; sensor 1; group 2
T51-T53
90–240 V AC/DC; PT100; sensor 2; group 2
T61-T63
90–240 V AC/DC; PT100; sensor 3; group 2
51/52/54
90–240 V AC/DC
Relay output limit value group 1 reached; (changeover contact)
61/62/64
90–240 V AC/DC
Relay output limit value group 2 reached; (changeover contact)
Ground _
OUT 1
U1
OUT 1
I1
OUT 1
0/4–20 mA
0/2–10V
Analog output out 1, sensor group 1
Ground _
OUT 2
U2
OUT 2
I2
OUT 2
0/4–20 mA
0/2–10V
Analog output out 2, sensor group 2
Max. connectable cross-section: 2.5 mm² (AWG 12)
Diagnosis
Messages output during operation and in the event of faults (meaning of LEDs on -A140) are
described in the lug "Additional Operating Instructions" of the Operating Instructions.