Diagnosis / faults and alarms
10.2 Diagnosis
Drive converter cabinet units
418
Operating Instructions, 07/07, A5E00288214A
Vector: key diagnostic parameters (details in List Manual)
Name
Parameters
Description
Operating display
r0002
The value provides information about the current operating status and the conditions necessary to reach the
next status.
Speed setpoint smoothed
r0020
Displays the actual smoothed speed/velocity setpoint at the input of the speed/velocity controller or V/f
characteristic (after the interpolator).
Actual speed smoothed
r0021
Displays the smoothed actual value of the motor speed/velocity.
DC link voltage smoothed
r0026
Displays the smoothed actual value of the DC link.
Absolute actual current smoothed
r0027
Displays the smoothed actual value of the current.
Actual torque smoothed
r0031
Displays the smoothed actual torque.
Motor temperature
r0035
If r0035 does not equal -200.0 °C, the following applies:
•
This temperature indicator is valid.
•
An KTY sensor is connected.
•
If using an asynchronous motor, the thermal motor model is activated (p0600 = 0 or p0601 = 0).
If r0035 equals -200.0 °C, the following applies:
•
This temperature indicator is invalid (temperature sensor fault).
•
An PTC sensor is connected.
If using a synchronous motor, the thermal motor model is activated (p0600 = 0 or p0601 = 0).
Power Module temperatures
r0037
Displays the measured temperatures in the Power Module.
Missing drive enable signals
r0046
Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
Motor/encoder data set effective (MDS, EDS)
r0049
Displays the effective motor data set (MDS) and the effective encoder data sets (EDS).
Command data set effective (CDS)
r0050
Displays the effective command data set (CDS)
Drive data set (DDS) effective
r0051
Effective drive data set (DDS) display.
Rated power module power
r0206
Displays the rated power module power for various load duty cycles.
Rated power module current
r0207
Displays the rated power module power for various load duty cycles.
Rated power module line supply voltage
r0208
Displays the rated line supply voltage of the power module.