Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
483
12.3.1
Cabinet unit version A, 380 V - 480 V 3 AC
Table 12-9 Version A, 380 V – 480 V 3 AC, part 1
Category
Unit
Order no. 6SL3710-
7LE32-1AA0
7LE32-6AA0
7LE33-1AA0
Rated motor output
at 400 V, 50 Hz
at 460 V, 60 Hz
kW
hp
110
150
132
200
160
250
Rated input voltage
V
380 V to 480 V 3 AC ± 10% (-15% < 1 min)
Rated input current
1)
A
197
242
286
Rated output current
A
210
260
310
Base-load current I
L2)
A
205
250
302
Base-load current I
H3)
A
178
233
277
Max. output frequency
4)
Hz
160
160
160
Power loss
kW
5,6
6,6
8,5
Cooling air requirement
m³/s
0,58
0,70
1,19
Sound pressure level at 50/60 Hz dB(A)
71/73
71/73
72/74
Line connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 70
4 x 240
4 x (500)
M12 (2 holes)
2 x 95
4 x 240
4 x (500)
M12 (2 holes)
2 x 120
4 x 240
4 x (500)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 70
2 x 150
2 x (300)
M12 (2 holes)
2 x 95
2 x 150
2 x (300)
M12 (2 holes)
2 x 120
2 x 150
2 x (300)
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard version) kg
708
708
892
Frame sizes
Active Interface Module
Active Line Module
Motor Module
FI
FX
FX
FI
FX
FX
GI
GX
GX
Dimensions (standard version)
Width x height x depth
mm
1400 x 2,000 x 600
1400 x 2,000 x 600
1400 x 2,000 x 600
Recommended protection
Line protection
(with option L26)
Rated current
Frame size to DIN 43620-1
Line and semi-cond. protection
(without option L26)
Rated current
Frame size to DIN 43620-1
A
A
3NA3252
315
2
3NE1230-2
315
1
3NA3254
355
2
3NE1331-2
350
2
3NA3365
500
3
3NE1334-2
500
2
1)
The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for
example, with options L19 or B03).
2)
The base-load current (I
L
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
3)
The base-load current (I
H
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
4)
Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency,
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see
"Derating data").
5)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
(National Electrical Code) or CEC (Canadian Electrical Code) standards.