Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
289
●
OFF2
–
Immediate pulse suppression, the drive coasts to standstill.
–
The motor brake (if parameterized) is closed immediately.
–
Switching on inhibited is activated.
●
OFF3
–
Switch to speed-controlled operation
–
n_set = 0 is input immediately to brake the drive along the OFF3 deceleration ramp
(p1135).
–
When standstill is detected, the motor brake (if parameterized) is closed.
–
The pulses are inhibited when the motor brake closing time (p1217) has elapsed.
Standstill is detected when the speed actual value of the speed threshold (p1226) is
undershot or when the monitoring time (p1227) started when speed setpoint ≤ speed
threshold (p1226) expires.
–
Switching on inhibited is activated.
Function diagram
FP 6060
Torque setpoint
Parameters
•
p0341
Motor moment of inertia
•
p0342
Ratio between the total and motor moment of inertia
•
p1300
Open-loop/closed-loop control mode
•
p1499
Accelerating for torque control, scaling
•
p1501
Change over between closed-loop speed/torque control
•
p1503
Torque setpoint
•
p1511
Supplementary torque 1
•
p1512
Supplementary torque 1 scaling
•
p1513
Supplementary torque 2
•
p1514
Supplementary torque 2 scaling
•
r1515
Supplementary torque total