Functions, monitoring, and protective functions
9.5 Monitoring and protective functions
Drive converter cabinet units
406
Operating Instructions, 07/07, A5E00288214A
Sensor monitoring for wire breakage/short-circuit
If the temperature of the motor temperature monitor is outside the range –50°C to +250°C,
the sensor cable is broken or has short-circuited. Alarm A07915 ("Alarm: temperature sensor
fault") is triggered. Fault F07016 (“Fault: temperature sensor fault”) is triggered once the
waiting time defined in p0607 has elapsed.
Fault F07016 can be suppressed by p0607 = 0. If an induction motor is connected, the drive
continues operating with the data calculated in the thermal motor model.
If the system detects that the motor temperature sensor set in p0600 is not connected, alarm
A07820 "Temperature sensor not connected" is triggered.
Function diagram
FD 8016
Thermal monitoring motor
FD 9576
TM31 -temperature evaluation KTY/PTC
FD 9577
TM31 -sensor monitoring KTY/PTC
Parameters
•
p0600
Motor temperature sensor for monitoring
•
p0604
Motor overtemperature alarm threshold
•
p0605
Motor overtemperature fault threshold
•
p0606
Motor overtemperature timer
•
p0607
Temperature sensor fault timer
•
p0610
Response to motor overtemperature condition
•
p4100
Temperature evaluation sensor type