Operation
6.6 PROFIBUS
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
211
6.6.6
Description of status words and actual values
Overview
Table 6-14 Overview of status words and actual values
Abbreviation
Description
Parameters
Function diagram
ZSW 1
Status word 1 (interface mode SINAMICS /
MICROMASTER, p2038 = 0)"
See table "Status word 1 (interface
mode SINAMICS /
MICROMASTER, p2038 = 0)"
FP2452
ZSW 1
Status word 1 (interface mode PROFIdrive
VIK-NAMUR, p2038 = 2)
See table "Status word 1 (interface
mode PROFIdrive VIK-NAMUR,
p2038 = 2)"
FP2451
N_act_A
Speed setpoint A (16 bit)
r0063[0]
FP4715
N_act_B
Speed setpoint B (32 bit)
r0063
FP4710
Ia_act
Actual value of current
r0068[0]
FP6714
M_act
Actual torque value
r0080[0]
FP6714
P_act
Actual power value
r0082[0]
FP6714
N_act_SMOOTH
Actual speed smoothed
r0063[1]
FP4715
Ia_act_SMOOTH
Current actual value, smoothed
r0068[1]
FP6714
M_act_SMOOTH
Torque actual value, smoothed
r0080[1]
FP6714
P_act_SMOOTH
Power actual value, smoothed
r0082[1]
FP6714
MELD_NAMUR
VIK-NAMUR message bit bar
r3113, see table "NAMUR
message bit bar"
--
WARN_CODE
Alarm code
r2132
FP8065
ERROR_CODE
Error code
r2131
FP8060
Status word 1 (interface mode SINAMICS / MICROMASTER, p2038 = 0)"
Table 6-15 Status word 1 (interface mode SINAMICS / MICROMASTER, p2038 = 0)"
Bit
Meaning
Explanation
BICO
1 Ready to power up
Power supply on, electronics initialized, line contactor
released if necessary, pulses inhibited.
0
Ready to power up
0 Not ready to power up
BO: r0899.0
1 Ready
Voltage at Line Module (i.e. line contactor closed (if used)),
field being built up.
1
Ready
0 Not ready
Cause: No ON command has been issued.
BO: r0899.1
1 Operation enabled
Enable electronics and pulses, then ramp up to active
setpoint.
2
Operation enabled
0 Operation inhibited
BO: r0899.2