Depending on the setting in p0922, the interface mode of the control and status word is
automatically set:
●
p0922 = 1, 352, 999:
STW 1/ZSW 1: Interface Mode SINAMICS / MICROMASTER, p2038 = 0
●
p0922 = 20:
STW 1/ZSW 1: Interface Mode PROFIdrive VIK-NAMUR, p2038 = 2
b. Telegrams for "basic positioner" function module
The following telegrams can be selected when the "basic positioner" function module is
activated (allocation: see FD2420):
•
p0922 = 7
-> Basic positioner (standard telegram)
•
p0922 = 110 -> Basic positioner (manufacturer-specific telegram)
c. Free telegrams (p0922 = 999)
Send and receive telegrams can be configured as required by using BICO technology to
interconnect the send and receive words. The default process data assigned under a) is
retained when a switchover is made to p0922 = 999, although it can be changed or
supplemented at any time.
To maintain compliance with the PROFIdrive profile, however, the following assignments
should be retained:
●
Interconnect PZD receive word 1 as control word 1 (CTW 1)
●
Interconnect PZD send word 1 as status word 1 (STW 1)
For more information about possible interconnections, see function diagrams FD2460 and
FD2470 and the simplified diagrams 620 to 622.
Structure of the telegrams
Table 6-10 Structure of the telegrams
Telegr.
PZD1
PZD2
PZD 3
PZD 4
PZD 5
PZD 6
PZD 7 PZD 8 PZD 9 PZD 10
STW 1 N_set_A
1
ZSW 1 N_act_A
STW 1
N_set_B
CTW2
2
ZSW 1
N_act_B
STW2
STW 1
N_set_B
CTW2
G1_CTW
3
ZSW 1
N_act_B
STW2
G1_STW
G1_XIST1
G1_XACT2
STW 1
N_set_B
CTW2
G1_CTW
4
ZSW 1
N_act_B
STW2
G1_STW
Further assignment, see FP2420
STW 1 N_set_A
20
ZSW 1 N_act_A
Ia_act_
SMOOTH
M_act_
SMOOTH
P_act_
SMOOTH
MELD_NA
MUR
STW 1 N_set_A
PCS_3
PCS7_4
PCS7_5
PCS7_6
352
ZSW 1 N_act_A
Ia_act_
SMOOTH
M_act_
SMOOTH
WARN_
CODE
FAULT_
CODE
STW 1
Free
Free
Free
Free
Free
Free
Free
Free
Free
999
ZSW 1
Free
Free
Free
Free
Free
Free
Free
Free
Free