Commissioning
5.5 First commissioning
Drive converter cabinet units
162
Operating Instructions, 07/07, A5E00288214A
Basic commissioning: Selecting the motor type and entering the motor data
)
)
)
)
)
,(&>+]N:@
&RQWLQ
&RQWLQ
^9(&725`PRWRUVWDQGDUGPRWRUW\SH
S0RWRU6WDQGDUG,(&1(0$
SP0RWRUW\SHVHOHFWLRQ
$V\QFBPRWRU
+HOS
2.
You can select the motor standard and
type in the dialog screen.
The following is defined for the motor
standard:
0: Line frequency 50 Hz, motor data in kW
1: line frequency 60 Hz, motor data in hp
The following selection options are
available for the motor type:
1: Induction motor
2: Permanent-field synchronous motor
5: Synchronous motor (separately-excited)
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
)
)
)
)
)
P
P
)
)
)
)
)
QDWXUDOFRROLQJ
%DFN
&RQWLQ
^9(&725`0RWRUSDUDPHWHUV
S6XSSO\YROWDJH
SP0RW8BUDWHG
9UPV
9
SP0RW,BUDWHG
$UPV
SP0RW3BUDWHG
N:
+HOS
2.
^9(&725`0RWRUSDUDPHWHUV
SP0RWFRVSKLBUDWHG
SP0RWIBUDWHG
+]
SP0RWQBUDWHG
USP
SP0RWRUFRROLQJW\SH
+HOS
2.
Entering motor data specified on the type
plate
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
To change a parameter value, navigate to
the required selection field and activate
with <F5>.
The system displays another window in
which you can:
•
Enter the value directly, or
•
select the value from a list.
When you have finished entering the motor
data, choose "Continue" underneath the
final parameter value and activate your
entries with <F5>.
Note
The steps described below also apply to induction motors.
When commissioning a permanent-field synchronous motor (p0300 = 2), there are a few
special conditions that apply, which are detailed in a separate chapter (see "Setpoint
channel and closed-loop control/Permanent-field synchronous motors").