Replace the air filter.
Electrical Control
●
Perform routine check on all electrical components and safety devices.
●
Periodically check valves that control the flow of media.
●
Check whether the grounding devices of the electric devices are complete and
functional.
●
Check the performance of safety protection devices such as air circuit breakers
and AC contactors to ensure their safety and reliability.
Smart Cooling Product Structure
●
Apply lubricants to all locking fixtures for lubrication.
●
Repair the damaged parts to avoid corrosion.
●
Check the air tightness and connection.
Common Faults
If an exception occurs during the running of the smart cooling product, locate the
fault immediately. You can continue to use the smart cooling product only after
you rectify the fault. Do not use the smart cooling product if the fault is not
rectified to prevent unpredictable losses.
NO TICE
Before performing any operation on the smart cooling product, disconnect the
power supply.
Table 10-2 Troubleshooting of simple faults
Symptom
Possible Cause
Solution
Air leakage
The connection nut is loose
due to long-distance
transportation.
Tighten the screws.
The smart cooling product is
deformed after being
improperly transported or
installed.
Adjust the installation
position of the smart cooling
product.
Water leakage
● The water pan leaks.
● The drainpipe leaks or is
blocked.
● Repair or replace the
water pan.
● Replace the drainpipe.
The water pan
is not properly
drained.
The base is not properly
installed.
Level the base.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual