Figure 5-7 Installing an air duct
(1) Indoor return air duct
(end)
(2) Indoor supply air duct
(3) Indoor return air duct
(side)
NO TE
● The air duct must be wrapped with thermal insulation foam, and the thickness of the
thermal insulation foam must be greater than or equal to 3 cm.
● The joint between the air duct and the unit should be sealed to prevent air leakage.
Generally, the sealing cotton is pressed inside the flange of the air duct or sealant is
applied to the flange after installation.
----End
5.4.5 Installing Pipes
The designed height of the water trap must meet the requirements specified in
.
Figure 5-8 Designed height of the water trap
NO TE
It is recommended that the height of segment B be as low as possible.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
5 System Installation (FDC Scenario)