5.5.3 Cable Routes
Figure 5-18 Cable routes
(1) Power cable
(2) Signal cable
5.5.4 (Optional) Installing Teamwork and Monitoring
Communications Cables
NO TICE
● Smart cooling products of different models and software versions cannot be
networked for teamwork.
● Connect teamwork and monitoring communications cables based on the
networking scenario.
● The teamwork communications cable must be a shielded network cable of Cat
5e or higher specifications. The network cable length between adjacent units
must be less than or equal to 100 m, and the maximum distance for CAN
teamwork communication must be less than or equal to 310 m.
● Route cables in compliance with local standards. Take appropriate shielding
measures, such as using a galvanized pipe or an ELV cable tray, to reduce the
impact of electromagnetic interference on teamwork communication.
Otherwise, teamwork networking may fail.
5.5.4.1 Preparing a Network Cable
Step 1 Crimp a network cable.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
5 System Installation (FDC Scenario)