Step 6 Flip the clip to lock the fan drive.
Figure 12-42 Installing the fan drive
Step 7 Power on the unit, and choose Maint > Wizard Startup on the home screen. Start
the fan and check that the fan works properly without any alarms. Check that the
smart cooling product works properly before you exit.
----End
12.19 Replacing a Liquid Level Sensor
Prerequisites
●
A liquid level sensor needs to be replaced.
●
A spare liquid level sensor of the same model is available and functional.
●
Tool: solid wrench
Context
The liquid level sensor can be maintained only at the water tank.
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
NO TICE
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the maintenance door.
Step 3 Replace the liquid level sensor in the spray water tank.
●
Open the water tank cover.
●
Cut off the cable tie that secures the liquid level sensor cable, and remove the
interconnection terminal.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
192