Figure 13-12 Alarm details
Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults by
following instructions in the diagnosis report.
----End
Follow-up Procedure
To query historical alarms, choose Common Function > Query Hist Alarms on
the home screen or choose Alarms > Query Hist Alarms on the home screen.
NO TE
Historical alarms are displayed in chronological order. The latest cleared alarm is displayed
in the uppermost row.
13.2.11 How Do I Clear Component Runtime?
Context
NO TICE
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken the
performance of the unit.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End
13.2.12 How Do I Calibrate a T/H Sensor?
Context
Calibrate a sensor if the displayed temperature or humidity values on the sensor
deviate from the actual values. For example, if the return air temperature
measured by other precise temperature measurement units at the return air
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual