Symptom
Possible Cause
Solution
The drainpipe does not have
a water trap or does not
meet the requirements.
Install or adjust the water
trap.
The fan works
abnormally.
The fan bearing is worn out.
Repair or replace the bearing.
The fan blade is interfered
with the shell.
Adjust the fan blade.
There is foreign matter.
Clear foreign matter.
The air volume
is excessively
large.
The external static pressure is
excessively small (the air
duct is excessively short).
Balance the air volume and
air pressure.
The fan motor
is burnt out.
The motor is overloaded.
Balance the air volume and
replace the fan.
The motor is poorly
insulated.
Replace the fan.
The running
sound is
abnormal.
The compressor, fan, or pipes
are loose.
Check and secure loose parts.
The air damper is shaking.
Adjust the air damper.
The compressor
does not work.
The high-pressure switch is
triggered.
Check the high-pressure
switch.
The circuit breaker, fuse, or
cable is disconnected.
Check the main circuit
breaker, compressor circuit
breaker, fuses, and cables.
The compressor motor is
damaged.
Check whether the motor is
damaged and needs to be
replaced.
The compressor does not
need to be started.
Check the requirement status
on the display module.
The drive is faulty.
Replace the drive.
The compressor
discharge
temperature is
too high.
The refrigerant loop or
component is blocked.
Clean up foreign matter in
the refrigerant loop.
Air enters the refrigerant
loop.
Exhaust air and repair the
pipeline.
Heat dissipation is poor
because the condenser is
dirty or blocked.
Clean the condenser fins.
The exhaust fan is faulty.
Check whether the exhaust
fan works properly.
The refrigerant is insufficient. Charge more refrigerant.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
10 Troubleshooting
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
148