Figure 4-22 Connecting communications cables
----End
4.5.4.4 FE Te RS485 Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
FE Teamwork
RS485 Monitoring
Protocol
MAC_CAN
Modbus-RTU
Note
A teamwork network supports
a maximum of 16 units.
It takes 3 x
n
seconds to
collect data from
n
units. If
the time required for the host
to collect data from all units
does not meet the
performance requirements,
group the units.
● If units are not grouped (
n
= 1), set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for each unit.
● If units are grouped (
n
> 1;
recommended:
n
≤ 4), set
RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the unit with the
COM/FE port connected.
Retain the default setting
(Disable) for other units.
NO TE
● Connect the COM/FE port on the main control module of the last unit in each group to
the RS485 port on the host.
● Customers can purchase an ECC and NetEco as the monitoring system.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (Building Scenario)