Loosen the nut on the liquid level sensor using a wrench and take out the
sensor from the water tank.
Figure 12-43 Removing a liquid level sensor
(1) Water tank cover
(2) Liquid level sensor
Step 4 Replace the liquid level sensor at the bottom of the precooling module.
●
Remove the adjustable side panel and water barrier of the air supply fan.
●
Cut off the cable tie that secures the liquid level sensor cable, and remove the
interconnection terminal.
●
Remove the fastener from the liquid level sensor at the bottom of the
precooling module.
●
Loosen the nut on the liquid level sensor using a wrench and take out the
sensor.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
193