Context
NO TICE
Before checking and maintaining the device, ensure that the primary power supply
to the device is disconnected and the drive has been powered off for 10 minutes.
Otherwise, electrical shocks may occur.
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
NO TICE
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the maintenance door.
Step 3 Remove all cables from the drive and cut the cable ties using diagonal pliers.
Step 4 Remove the four screws on the drive using a Phillips screwdriver, and pull out the
drive.
Figure 12-40 Removing a drive
Step 5 Install the new drive.
Step 6 Connect the cables to the drive.
Step 7 Power on the unit, and choose Maint > Wizard Startup on the home screen. Start
the compressor and check that the compressor works properly without any alarms.
Check that the smart cooling product works properly before you exit.
----End
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
190