Item
Building Scenario
Air filter level on
the outdoor air
intake side (EN
779)
G3
Fan type
EC
Air volume
Indoor: 55,000 m
3
/h
Outdoor: 50,000 m
3
/h
Net weight
5000 kg
Operating weight 5500 kg
1
Test conditions: The outdoor dry and wet bulb temperatures are 35°C and 27°C
respectively; the indoor return and supply air temperatures are 38°C at 25% RH
and 25°C at 50% RH respectively; the external residual pressures of the indoor
and outdoor units are 150 Pa and 100 Pa respectively. If the indoor return air
temperature is lower than 38°C, the cooling capacity of the equipment is
derated.
Table 3-2 Compressor cooling specifications
Item
Specifications
Compressor type
Variable-frequency scroll compressor
Number of compressors
3
Throttling device
Electronic expansion valve (EEV)
Refrigerant
R410A
3.1.2 System Specifications (FDC Scenario)
Table 3-3 System specifications
Item
FDC Scenario
Maximum power
78.5 kW (default power)
Maximum
current
140 A (default current)
Total cooling
capacity
240 kW
1
Sensible cooling
capacity
240 kW
1
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3 Product Specifications
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
29