3.2 Operating Environment Specifications
Environmental Specifications
Table 3-5 Environmental specifications
Item
Specifications
Operating
temperature
–40°C to +45°C
Operating humidity
5%–95% RH
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH
Altitude
The performance is not derated when the altitude is
below 1000 m, and is derated when the altitude ranges
from 1000 m to 4000 m.
Table 3-6 Derating coefficients
Altitude
(m)
1000
1500
2000
2500
3000
3500
4000
Air volume
coefficient
0.887
0.835
0.785 0.737
0.692
0.649
0.608
Cooling
capacity
coefficient
0.887
0.835
0.785 0.737
0.692
0.649
0.608
Installation Requirements
NO TICE
If the total actual load of servers for each equipment is less than 10% of the rated
cooling capacity or the equipment room is not properly sealed, the humidity in the
equipment room may exceed the upper limit, which is not a product quality issue
and should be dealt with by adding a dehumidifier.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3 Product Specifications
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
31