Figure 4-14 Setting sealing putty
(1) Paper protective film
(2) Sealing putty (standard configuration)
Pipe Anti-freezing
When the ambient temperature is less than or equal to 0°C, drainpipes and water
refill pipes may freeze and thereby be blocked or crack. Take anti-freezing
measures for the pipes.
4.4.6 Removing Transport Fasteners and Desiccant Bags
Procedure
Step 1 Remove the maintenance door of the compressors and take out the desiccant
bags from the compressors.
Step 2 Open the electric control box and take out the desiccant bag from the box.
Step 3 Open the outdoor intake air filter and take out the desiccant bag from the
outdoor air intake compartment.
Step 4 Open the maintenance door and water barrier of the spray pump, and take out
the two desiccant bags from the spray pump compartment.
Step 5 Loosen the transport fixing bolts of the three compressors using a 13# solid
wrench and remove the sheet metal fasteners.
Figure 4-15 Removing sheet metal fasteners from a compressor
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (Building Scenario)
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
49