Tool: Phillips screwdriver
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
NO TICE
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Remove the sealing plates.
Step 3 Remove the screws from the NTC temperature sensor fastener, and take out the
fastener.
Figure 12-17 Replacing an NTC temperature sensor
Step 4 Remove the screws that secure the NTC temperature sensor.
Step 5 Remove the interconnection terminal from the cable of the NTC temperature
sensor.
Step 6 Install the new NTC temperature sensor, reconnect the cables, and secure the NTC
temperature sensor in the original position.
Step 7 Power on the unit and tap Start on the home screen. Ensure that the unit is
running normally without any alarms.
----End
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
167