Figure 5-5 Securing the unit
(1) Maintenance door
Step 5 Hoist the other unit.
Step 6 Place it on the top of the installed unit (ensure that the contact surface is clean).
Step 7 Secure the units at the upper and lower layers.
Step 8 Close the maintenance door after the units are secured.
----End
5.4.3 Checking the Refrigerant
Procedure
Step 1 Open the maintenance door to the compressors.
Step 2 Check whether any needle valve bonnet of the compressors is missing.
1. If any bonnet is missing, contact Huawei technical support.
2. If no bonnet is missing, remove the valve bonnets, and press the valve plugs
using the valve bonnets in turn. If gas flows out, the system is normal. If no
gas flows out, contact Huawei technical support.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
5 System Installation (FDC Scenario)
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
76