No.
Item
Note
12
Teamwork control
button
●
indicates that teamwork control is
disabled.
●
indicates that teamwork control is
enabled and no teamwork control alarm is
generated.
●
indicates that teamwork control is
enabled and a teamwork control alarm is
generated.
7.4 Initial Configuration
Log in as the admin user (preset password: 000001) when setting initial
parameters.
7.4.1 Setting T/H Sensor Parameters
Prerequisites
●
The T/H sensors outside the unit need to be enabled when they are installed;
otherwise, retain the default settings.
●
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Figure 7-3 T/H Sensor
Step 2 Set Cold aisle sensor 1 to Enable.
Step 3 Set temperature and humidity parameters.
NO TE
You are not advised to modify the parameters that are not listed in the following table.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
7 Power-On Commissioning
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
113