12.6 Replacing a Differential Pressure Switch (FDC
Scenario)
Prerequisites
●
A differential pressure switch needs to be replaced.
●
A spare differential pressure switch of the same model is available and
functional.
●
Tool: Phillips screwdriver
Context
The differential pressure switch can be maintained from the end only after the air
filter is removed.
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
NO TICE
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Remove the outdoor intake air filter.
Step 3 Remove the bolts from the sheet metal, flip the plate, and remove the sheet metal
and differential pressure switch.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
159