Tab
Parameter
Description
Date and
Time Settings
Date format
Specifies the date format.
Date settings
Specifies the date.
Time zone
Specifies the time zone.
Time
Specifies the time.
Teamwork
Settings
Teamwork group No.
Specifies the planned teamwork group
number. This parameter should be the
same for all units in the same
teamwork group.
System address
Specifies the planned unit address. The
addresses of units in the same
teamwork group must be unique.
Networking mode
Specifies the networking mode for
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Teamwork function
Specifies whether to enable the
teamwork function. Set this parameter
based on onsite heat load distribution.
● Disable: A unit operates
independently.
● Enable: A unit operates in team
with other units.
Number of systems in
this group
Specifies the total number of units in
this group. The value is an integer
ranging from 1 to 32.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Number of running
systems in this group
Specifies the number of running units
in this group. The value is an integer
ranging from 1 to the value of
Number of systems in this group.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Teamwork power limit
function
Limits the power of the teamwork
group.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
7 Power-On Commissioning
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
103